Product Details:
Payment & Shipping Terms:
|
Model: | Flatpack2 380/3000 HE | Part Number: | 241119.825 |
---|---|---|---|
Current: | 18.2 ARMS | Power: | 3000 W |
Power @ 85 VAC: | 1200 W | Hold Up Time: | > 20 Ms |
Efficiency @ 230 VAC Input: | > 96.2% | MTBF: | >400 000 (@ Tambient : 25 °C) |
High Light: | Eltek Flatpack2 380V,Eltek Flatpack2 3000W,241119.825 |
Eltek Flatpack2 380V Rectifier 380/3000 HE Doc 241119.825. DS3 - v3.2
Key Features
Power Density - 33 w/Inch3
High Efficiency – 96.2%
Or-Ing Protection On Output
Hot Pluggable – Mttr < 5 Min
Voltage Keying
Applications
DATA CENTER
Centralized battery back-up systems
TELECOM
Central office / large switch sites OTHER INDUSTRIES
380VDC UPS
Overview
HE rectifier for 380VDC in data centers
The Flatpack2 380/3000 HE rectifier has high efficiency, ORing protection on output and high output power.
Distribute pure battery backup DC voltage with a minimum of loss. Remove the low reliability DC-AC step in the central backup power system and maximize its reliability and efficiency.
Stack cabinets with up to 72 rectifiers to build large power systems monitored by the Smartpack2 controller.
Specifications
Model | Flatpack2 380/3000 HE |
Part number | 241119.825 |
INPUT DATA | |
Voltage (nominal) | 176 - 277 VAC |
Voltage (range) | 85 - 305 VAC |
Frequency | 45 - 66 Hz |
Current (maximum) @ nominal input, full load | 18.2 ARMS |
Power Factor | > 0.99 at 50% load or more |
Protection |
Fuse in L & N Varistor Disconnect when VIN is out of range |
OUTPUT DATA | |
Voltage (default) | 381 VDC |
Voltage (adjustable range) | 300 - 400 VDC |
# Pb cell supported | 156 - 168 1) |
Power (maximum) | 3000 W |
Power @ 85 VAC | 1200 W |
Current (maximum) @ nominal input, full load | 9 A (@VOUT < 336 VDC) / 7.9 A (@ VOUT = 381 VDC) |
Current sharing (10 - 100% load) | ±5% of maximum current from 10 to 100% load |
Static Voltage regulation (10 - 100% load) | ±0.5% |
Dynamic Voltage regulation | ±5.0% for 10-50% or 50-10% load variation, regulation time < 25 ms |
Hold up time | > 20 ms; output voltage > 300 VDC at 1500 W load |
Ripple | < 1000 mVP-P , 30 MHz bandwidth |
Protection |
Overvoltage shutdown Hot plug-in - Inrush current limiting ORing diode Short circuit proof High temperature protection |
OTHER SPECIFICATIONS | |
Efficiency @ 230 VAC input | > 96.2% |
Isolation |
3.0 kVAC – input to output, 1.5 kVAC – input to earth, 1.5 kVDC – output to earth, 3.0 kVAC – CAN to primary, 3.0 kVAC – CAN to secondary |
Alarms (Red LED) | Low mains shutdown, High and low temperature shutdown, Rectifier Failure, Overvoltage shutdown on output, Fan failure, Low voltage alarm, CAN bus failure |
Warnings (Yellow LED) | Rectifier in power derate mode, Remote battery current limit activated, Input voltage out of range, flashing at overvoltage |
Normal (Green LED) | Input and output ok |
Acoustic noise, at nominal input and full load | < 40dBA @Tambient< 25°C / <58dBA @ Tambient> 40°C |
MTBF (Telcordia SR-332 Issue I method III (a)) | >400 000 (@ Tambient : 25 °C) |
Operating temperature |
-40 to +75°C (-40 to +167°F), humidity 5 - 95% RH non-condensing Output power de-rates linear from 3000W @ 50°C (122°F) to 980W @ 75°C(167°F) |
Storage temperature | -40 to +85°C (-40 to +185°F), humidity 0 - 99% RH non-condensing |
Dimensions[WxHxD] / Weight | 109 x 41.5 x 327 mm (4.25 x 1.69 x 13”) / < 1.95 kg (4.3 lbs) |
DESIGN STANDARDS | |
Electrical safety | EN 60950-1:2006+A11:2009+A1:2010+A12:2011, IEC 60950-1:2005+A1:2009, UL 60950-1:2011, CSA C22.2 No. 60950-1-07 |
EMC |
EN 61000-6-1:2007, -6-2:2005, -6-3:2007 + A1:2011, -6-4:2007 + A1:2011, EN 300 386:v1.6.1, FCC CFR 47 Part 15:2013 |
Environment | ETSI EN 300 019: 2-1 (Class 1.2), 2-2 (Class 2.3) & 2-3 (Class 3.2) 2011/65/EU (RoHS) & 2008/98/EC (WEEE) |
1) for 156 cells minimum test voltage is 1.923 V/cell. For 168 cell maximum boost voltage is 2.38 V/cell |
Smartpack2 system controller
72 rectifiers power cabinet
Contact Person: Mr. Cocoon Lee
Tel: +8615625220987
Fax: 86-27-82757025