Product Details:
Payment & Shipping Terms:
|
Efficiency: | 92% | Frequency: | 45-65Hz |
---|---|---|---|
Power Factor: | >=0.99 | Input Voltage: | 80-300VAC |
Tem Range: | -40~+75℃ | Output Power: | 1000W@Vout>48VDC |
High Light: | netsure 211c46,emerson netsure 211 |
Vertiv Emerson Embeded Power Supply 2-4KW Netsure 211C46 3G FTTx Data Networks
Short Description
The NetSure 211 DC Power Solution is a flexible system capable of providing DC power through the use of 500 W or 1000 W rectifiers and a variety of output distribution options. The system is available in an integrated distribution configuration. The NetSure 211 is available in both 19" and 23" 1 RU & 2 RU rack-mount configurations, suited for up to 6 kW power requirements in the most harsh environments. The system is supported by a single SCU+, ACU+ or NCU controller (ACU+ for 2 RU systems only) that provides all control and operational conditions, as well as historical site data and external signal conditioning and monitoring. Each rectifier shelf includes a slot for the controller and space for the rectifiers. Distribution is provided by breakers or fuses located in the power shelf. Distribution options include load low-voltage disconnect (LLVD), battery low-voltage disconnect (BLVD), or no low-voltage disconnect. Plug-in rectifiers, AC connectivity and DC load outputs enhance the overall flexibility of the system by minimizing installation and start-up time. This dynamic system also offers alternative AC input configurations, relay rack configurations, battery tray options, battery box options and pre-configured output load kits. The NetSure 211 is designed for up to 4 kW loads (19") or 6 kW loads (23"). This cost-effective solution is NEBS Level 3 compliant and UL Listed. Rated for continuous operation from -40 °C to +75 °C (see rectifier data for derating), this system is designed for the harsh outside plant environment, as well as customer premise FTTx, wireless back-haul, microwave, and DLC applications.
*Standard 19 inch sub rack with light weight, saving room space and installation cost
*Full front operation,convenient for maintenance
Features
* Extra wide input voltage range, strong power grid adaptability
* Wide operating temperature range for rectifier and controller, hot swappable , online maintenance
* The monitoring module can sabe up to 200 pieces of historical alram records, and 10 sets of battery test date records
* Perfect battery management effectively prolongs battery service life.
* RS232 port, Ethernet, dry contacts and other communication ports provided, flexible networking is enabled to achieve remote monitoring functions
* The system has complete fault protection and fault alarm functions
Specifications
Model Number | NetSure 211 C46 |
Output Type | Single |
Input Voltage | 90~290vac |
Output Voltage | 48V |
Output Frequency | >500W |
Output Current | 80A |
Weight | 15 |
Selling Units | Single item |
Single package size | 50X30X15 cm |
Single gross weight | 15 KG |
Package Type | Original and New Packaging |
Contact Person: Mr. Cocoon Lee
Tel: +8615625220987
Fax: 86-27-82757025